Product details |
Home - Products Class |
High Yield
• |
Efficient three-level topology, max. efficiency up to 99 %, European efficiency 98.7 % |
• |
Full power operation without derating at 50 ℃ |
• |
Long-time overload at 1.1 Pn |
• |
DC/AC ratio up to 1.5 |
Easy O&M
• |
Integrated zone current monitoring function for fast trouble shooting |
• |
Modular design easy for maintenance |
• |
IP65 protection |
Saved Investment
• |
Can be connected to double-winding transformer, saving transformer costs |
• |
Integrated SVG function |
Grid Support
• |
Compliance with standards: CE, IEC 62109, IEC 61727, IEC 62116 |
• |
Low/High voltage ride through (L/HVRT) |
• |
Active & reactive power control and power ramp rate control |
Technical Data
Input (DC) |
SG1250UD |
SG1500UD |
Max. PV input voltage |
1100 V |
Min. PV input voltage / Startup input voltage |
520 V / 540 V |
580 V / 600 V |
MPP voltage range for nominal power |
520 – 850 V |
580 – 850 V |
No. of independent MPP inputs |
2 |
No. of DC inputs |
16 |
Max. PV input current |
2712 A |
2896 A |
Max. DC short-circuit current |
3200 A |
Output (AC) |
|
|
Nominal AC power |
1386 kVA @ 45 ˚C / 1260 kVA @ 50 ˚C |
1650 kVA @ 45 ˚C / 1500 kVA @ 50 ˚C |
Max. AC output current |
2222 A |
2381 A |
Nominal AC voltage |
360 V |
400 V |
AC voltage range |
288 – 414 V |
320 – 460 V |
Nominal grid frequency / Grid frequency range |
50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz |
THD |
< 3 % (at nominal power) |
DC current injection |
< 0.5 % of nominal output current |
Power factor at nominal power / Adjustable power factor |
> 0.99 / 0.8 leading – 0.8 lagging |
Feed-in phases / Connection phases |
3 / 3 |
Efficiency |
|
|
Max. efficiency / Euro. efficiency |
99.0 % / 98.7 % |
Protection |
|
|
DC input protection |
Circuit breaker |
AC output protection |
Circuit breaker |
Overvoltage protection |
DC Type II / AC Type II |
Grid monitoring / Ground fault monitoring |
Yes / Yes |
Insulation monitoring |
Yes |
Overheat protection |
Yes |
Night SVG function |
Optional |
Anti-PID function |
Optional |
General Data |
|
|
Dimensions (W*H*D) |
2150*2120*850 mm |
Weight |
1900 kg |
Isolation method |
Transformerless |
Degree of protection |
IP65 |
Auxilury power supply |
220 Vac, 2 kVA |
Night power consumption |
< 40 W |
Operating ambient temperature range |
-35 to 60 ℃ (> 50 ℃ derating) |
Allowable relative humidity range (non-condensing) |
0 – 95 % |
Cooling method |
Temperature controlled forced air cooling |
Max. operating altitude |
4500 m (> 3000 m derating) |
Display |
Touch screen |
Communication |
RS485, Ethernet |
Compliance |
IEC62109-1, IEC62109-2, IEC61727, IEC62116 |
Grid support |
SVG(optional), LVRT, HVRT, active & reactive power control and power ramp rate control |
Type designation |
SG1250UD-10 |
SG1500UD-10 |
|
|
|