Centralized Inverter
High Yield
• | Efficient three-level topology, max. efficiency up to 99 %, European efficiency 98.7 % |
• | Full power operation without derating at 50 ℃ |
• | Long-time overload at 1.1 Pn |
• | DC/AC ratio up to 1.5 |
Easy O&M
• | Integrated zone current monitoring function for fast trouble shooting |
• | Modular design easy for maintenance |
• | IP65 protection |
Saved Investment
• | Can be connected to double-winding transformer, saving transformer costs |
• | Integrated SVG function |
Grid Support
• | Compliance with standards: CE, IEC 62109, IEC 61727, IEC 62116 |
• | Low/High voltage ride through (L/HVRT) |
• | Active & reactive power control and power ramp rate control |
Technical Data
Input (DC) | SG1250UD | SG1500UD |
Max. PV input voltage | 1100 V | |
Min. PV input voltage / Startup input voltage | 520 V / 540 V | 580 V / 600 V |
MPP voltage range for nominal power | 520 – 850 V | 580 – 850 V |
No. of independent MPP inputs | 2 | |
No. of DC inputs | 16 | |
Max. PV input current | 2712 A | 2896 A |
Max. DC short-circuit current | 3200 A |
Output (AC) | ||
Nominal AC power | 1386 kVA @ 45 ˚C / 1260 kVA @ 50 ˚C | 1650 kVA @ 45 ˚C / 1500 kVA @ 50 ˚C |
Max. AC output current | 2222 A | 2381 A |
Nominal AC voltage | 360 V | 400 V |
AC voltage range | 288 – 414 V | 320 – 460 V |
Nominal grid frequency / Grid frequency range | 50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz | |
THD | < 3 % (at nominal power) | |
DC current injection | < 0.5 % of nominal output current | |
Power factor at nominal power / Adjustable power factor | > 0.99 / 0.8 leading – 0.8 lagging | |
Feed-in phases / Connection phases | 3 / 3 |
Efficiency | ||
Max. efficiency / Euro. efficiency | 99.0 % / 98.7 % |
Protection | ||
DC input protection | Circuit breaker | |
AC output protection | Circuit breaker | |
Overvoltage protection | DC Type II / AC Type II | |
Grid monitoring / Ground fault monitoring | Yes / Yes | |
Insulation monitoring | Yes | |
Overheat protection | Yes | |
Night SVG function | Optional | |
Anti-PID function | Optional |
General Data | ||
Dimensions (W*H*D) | 2150*2120*850 mm | |
Weight | 1900 kg | |
Isolation method | Transformerless | |
Degree of protection | IP65 | |
Auxilury power supply | 220 Vac, 2 kVA | |
Night power consumption | < 40 W | |
Operating ambient temperature range | -35 to 60 ℃ (> 50 ℃ derating) | |
Allowable relative humidity range (non-condensing) | 0 – 95 % | |
Cooling method | Temperature controlled forced air cooling | |
Max. operating altitude | 4500 m (> 3000 m derating) | |
Display | Touch screen | |
Communication | RS485, Ethernet | |
Compliance | IEC62109-1, IEC62109-2, IEC61727, IEC62116 | |
Grid support | SVG(optional), LVRT, HVRT, active & reactive power control and power ramp rate control | |
Type designation | SG1250UD-10 | SG1500UD-10 |